We are going to check the tripping of a C 2A circuit breaker

00:08.249 --> 00:15.177
At 11 A, no trip

00:15.177 --> 00:23.372
A C 2 A curve must trip between 5 and 10 * In: between 10 A and 20 Amperes

00:23.372 --> 00:34.639
11.5 Amperes, still nothing

00:34.639 --> 00:52.893
It trips at about 12.5 Amperes: it is within its operating range!

00:52.893 --> 01:14.821
Now let's check the tripping current on overload

01:14.821 --> 01:21.585
We are going to time how long it takes to trip

01:21.585 --> 01:40.822
35 seconds at 2 * In, i.e. 4 Amperes: this confirms the C curve

01:40.822 --> 02:03.090
At 4 * In, about 8 Amperes: trips in less than 7 seconds