WEBVTT

00:00.000 --> 00:22.419
A model that can trip on magnetic-thermal or on thermal only

00:22.419 --> 00:34.062
So we are going to test only the short-circuit tripping

00:34.062 --> 00:45.465
We connect the adjustable current source, designed for short circuits, to the D 0.5 A breaker

00:45.465 --> 01:00.101
0.6 A; no trip, let's increase...

01:00.101 --> 01:13.622
DC or AC makes little difference to the value. 0.5 A curve D: 10 to 14 In, so between 5 and 7 Amperes

01:13.622 --> 01:38.463
5.5 Amperes, still no trip

01:38.463 --> 01:53.360
It tripped just above 7 Amperes!

01:53.360 --> 02:24.082
It trips at 7.5 Amperes, a little above its maximum value

02:24.082 --> 02:38.158
This 0.5 Ampere curve D trips at 15 * In (rated current)