00:00.000 --> 00:04.603
Diagram: Measurement of active and apparent power (wattmeter, ammeter and voltmeter)

00:04.603 --> 00:12.480
The wattmeter displays milli-Watt: so here 1880 mW

00:12.480 --> 00:22.184
The red ammeter (230 mA) in series, the yellow voltmeter in parallel on the coil

00:22.184 --> 00:32.920
The product U * I = 20 * 0.23 A = 4.6 "Watt", for only 1.9 Watt displayed!

00:32.920 --> 00:45.104
The product voltage * intensity is the apparent power supplied by the generator in VA!

00:45.104 --> 00:58.453
The Wattmeter displays the power actually converted (here mechanical to paste relay)

00:58.453 --> 01:13.498
The contact requires 1.9 W to stick but the coil absorbs 4.6 VA!

01:13.498 --> 01:26.817
The 'sources': inverters, transformers ... Indicates power in VA Volt * Ampere

01:26.817 --> 01:38.606
A 2 VA transformer would be insufficient! At least 4.6 VA to provide 2 W!

01:38.867 --> 01:49.391
1.9 / 4.6 (P in W / S in VA) = Cosine phi: cos phi = about 0.3 to 0.4 here

01:49.391 --> 01:56.459
EN green my capacitance which displays 33 μF for capacitors in blue disks.

01:56.459 --> 02:10.522
We will connect the 33 μF in parallel on the coil (at the level of the voltmeter) and observe I

02:10.522 --> 02:19.093
Apparent power bore its name badly: the generator supplies it, the wires transport it

02:19.093 --> 02:29.523
I carry out the paralleling in the level of the voltmeter, more practical and identical

02:29.523 --> 02:39.794
The intensity I is divided by 3! 76 mA against 230! S = 0.076 * 20.5 V = 1.5 VA approximately

02:39.794 --> 02:46.839
Now, with inaccuracies, P in Watt = S in VA! The decrease of P is an imprecision

02:46.839 --> 02:55.722
Here P drop, a little before in fact

02:55.722 --> 03:04.050
S in VA = P in Watt! So the cosine, cos phi = 1!

03:04.050 --> 03:12.029
It is now provided that the actually converted hence the name "power factor"

03:12.029 --> 03:18.702
For the cos phi, review video (same editing) with the oscilloscope as needed

03:18.702 --> 03:31.055
The electric efficiency is close to 1 when cos phi = 1 (remains the losses iron, Joule ...)

03:31.055 --> 03:42.049
Now you do not need to oversize the generator, cables and protections by a factor of 3!

03:42.049 --> 03:50.761
S is supplied by the generator, carried by the cables and absorbed by the receiver

03:50.761 --> 03:57.839
With S it produces Q its reagent: magnetic field that can be compensated

03:57.839 --> 04:06.310
It is indispensable, it can not be suppressed: it is compensated. It is he who produces the force

04:06.310 --> 04:16.530
The capacitors will produce the reagent useful to the coil for its magnetic field

04:16.530 --> 04:29.034
Spend everything in kW, Imagine: between a transformer 2 kVA (cos phi 1) and one of 5 kVA ...

04:29.034 --> 04:39.174
The difference in price, mass, space ...

04:39.174 --> 04:53.961
With Pythagoras one can easily find reactive power