The 24 VDC power supply controls a contactor via a pusher

00:06.495 --> 00:12.182
The continuous voltmeter is in parallel on the pusher (28 volts empty)

00:12.182 --> 00:20.238
In support of the voltage in the pusher is zero (0 V) but when I release ...

00:20.238 --> 00:30.987
Negative overvoltage is difficult to measure because it is very short but above 24 V!

00:30.987 --> 00:40.802
The surge is short car related to the stored energy

00:40.802 --> 00:52.358
When power is turned off, the coil tries to maintain the intensity and becomes the generator

00:52.358 --> 00:54.788
This has the effect of reversing the polarity of the voltage at its terminals

00:54.788 --> 01:03.980
With the attenuator, the LCD oscilloscope is on 400 Volts per vertical division

01:03.980 --> 01:11.416
The negative overvoltage was 3 divisions * 400 Volts = 1.2 kV

01:11.416 --> 01:22.425
The very violent reverse surge makes the oscilloscope 'crash'

01:22.425 --> 01:40.695
On the ground plane, no more worries EMC. The attenuated oscilloscope displays +/- 1,200 Volts maximum

01:40.695 --> 02:00.444
80 Volts * 20 (attenuator) = -1 600 Volts! (-1.6 kV)

02:00.444 --> 02:08.729
Another bug :-)!